High−level Instructions
3 − 531
Flag conditions
・Error flag (R9007): Turns on and stays on when:
・Error flag (R9008): Turns on for an instant when:
− The specified area is exceeded when an index is modified.
− The n is any value other than 0 or 2.
− The control code is outside specification range. (During instruction startup)
− The duty is higher than 100%. (During instruction startup)
− With the FP−X, the PWM output has not been set by the system register.
Data table settings
S Control code (*1)
S+1
Duty
(*2)
(*1): Control code specification (specify using K constant)
For FP Σ and FP−X
Resolution of 1000 Resolution of 100
K
Frequency
(Hz)
Timing
(ms)
K
Frequency
(Hz)
Timing
(ms)
K0 1.5 666.67 K20 15.6 k 0.06
K1 2.0 502.51 K21 20.8 k 0.05
K2 4.1 245.70 K22 25.0 k 0.04
K3 6.1 163.93 K23 31.3 k 0.03
K4 8.1 122.85 K24 41.7 k 0.02
K5 9.8 102.35
K6 19.5 51.20
K7 48.8 20.48
K8 97.7 10.24
K9 201.6 4.96
K10 403.2 2.48
K11 500.0 2.00
K12 694.4 1.44
K13 1.0 k 0.96
K14 1.3 k 0.80
K15 1.6 k 0.64
K16 2.1 k 0.48
K17 3.1 k 0.32
K18 6.3 k 0.16
K19 12.5 k 0.08
Note: When using ch2 or ch3 on FP−X Tr type, use the control codes up to K20.
(*2): Specification of duty (specify using K constant)
If the control code is K0 to K19, the duty is K0 to K999 (0.0% to 99.9%).
If the control code is K20 to K24, the duty is K0 to K99 (0% to 99%).
Set values are specified in units of 1% (K10) (digits below the decimal point are rounded off).