High−level Instructions
3 − 533
Outline Outputs the pulses from the specified channel for the pulse output
according to the specified data table.
Program example
Boolean
Ladder Diagram
Address Instruction
10
F174 SP0H , DT100 , K 0
S
n
Trigger
R10
DF
10
11
12
ST R 10
DF
F174 (SP0H)
DT 100
K0
S Starting address of area containing the data table.
n Channel for pulse output.
Operands
O
erand
Relay Timer/Counter Register
Index
register
Constant
Index
WX WY WR SV EV DT I K H
modifier
S N/A N/A N/A N/A N/A A N/A N/A N/A A
n N/A N/A N/A N/A N/A N/A N/A A A N/A
Description
When the corresponding control flag is off and the execution condition is in the on state, pulses are output
from the specified channel (ch0 or ch2) based on the contents set for the data table in which the first address
is that specified by “S”.
For FP Σ For FP−X Ry type (AFPX−PLS)
Channel no. Output Output method Channel no. Output Output method
ch0 Y0 CW PLS ch0
assete
mounting part 1
Y101 CCW SIGN
ch2 Y3 CW PLS ch1
assete
mounting part 2
Y201 CCW SIGN
FPΣ/FP−X
Pulse output
(with channel specification)
(Selectable data table control operation)
5
F174
(SP0H)
Availability
FPΣ/FP−X
A: Available
N/A: Not Available