High−level Instructions
3 − 662
Description
The output value (word data) stored in the area specified by D is controlled based on whether or not the input
value (word data) specified by S3 falls within the dead-band bounded by the upper and lower limits set in S1
and S2.
The output value is determined based on the following conditions:
When the lower limit S1 is greater than the input value S3, the input value S3 minus the lower limit value S1 is
stored in D as the output value.
When the upper limit S2 is less than the input value S3, the input value S3 minus the upper limit value S2 is
stored in D as the output value.
When Lower limit S1
Input value S3 Upper limit S2, zero is stored in D as the output value.
Output value D
In this range, zero is output.
Input value S3
Lower limit of
deadband S1
Upper limit of deadband S2
0
Flag conditions
・Error flag (R9007): Turns on and stays on when:
・Error flag (R9008): Turns on for an instant when:
− The area specified using the index modifier exceeds the limit.
− S1 > S2.
・Carry flag (R9009): Turns on for an instant when the calculated result is overflowed or
underflowed.
・= flag (R900B): Turns on when the input value is recognized as “0.