High−level Instructions
3 − 703
Outline This instruction calculates a natural logarithm LN( ).
For the FP0R/FPΣ/FP−X/FP0/FP−e, the P type high−level instruction
“P320 (PLN)” is not available.
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
S
Trigger
D
F320 LN, DT10, DT2010
R0
10
11
ST R 0
F320 (LN)
DT 10
DT 20
S Angle data (2 words) or lower 16-bit area of 32-bit data where angle data is
stored
D Lower 16-bit area of 32-bit data where calculated result is stored
Operands
O
p
erand
Relay Timer/Counter Register
Index
register
Constant
Index
modifier
Integer
device
Operand
WX WY WR WL SV EV DT LD FL I K H f
modifier device
S A A A A A A A A A A A A A A* A
D N/A A A A A A A A A A N/A N/A N/A A A
* Index modification of a real number is not possible.
Description
The natural logarithm LN(S+1 and S) is calculated of the data specified in S+1 and S, and the result is stored
in D+1 and D.
LN ([S+1, S]) → [D+1, D]
Specifying the integer device with [S], the integer data is internally converted to real numbers before
operations continue.
F320 LN, % DT 0, DT 4
R0
Specifying the integer device with [D], the real numbers are automatically converted into integer data.
F320 LN, DT 0, % DT 4
R0
F320
P320
(PLN)
(LN)
Floating point data natural logarithm
A
:
A
vailable
N/A: Not Available