1-1-16
11
Single-Type
1-1. Unit Specifications
Ducted Type S-140PE1R5B / U-140PZ2R5
INDOOR MODEL
S–140PE1R5B – –
PANEL MODEL
– – –
OUTDOOR MODEL
– U-140PZ2R5 –
Branch pipe MODEL
–
Performance test condition
ISO13253 / AS/NZS3823.1
Power supply
ø, Hz
1ø 50 Hz 1ø 50 Hz
V
– 230 V 240 V – 230 V 240 V Min Max
C
O
O
L
I
N
G
Capacity
kW
– 14.0 14.0 – – – 3.3 15.0
BTU/h
– 47800 47800 – – – 11300 51200
Current A
– 2.62 2.70 – 18.2 17.2 – –
Input power
W
– 590 640 – 3.850k 3.800k – –
TOTAL W
– – 4.440k 4.440k 1.090 5.970k
Annual consumption TOTAL kWh *
4
– – 2220 – – –
EER/ AEER/ STAR RATING TOTAL (W/W/-)
– – – –
3.15/3.11/-
3.15 3.03 2.51
Power factor %
– – – – 92 92 – –
Noise indoor
dB-A (H/M/L)
51/49/47 – – –
Power Level dB
73/71/69 – – –
Noise outdoor
dB-A (H/L)
– 56/– – –
Power Level dB
– 71/– – –
H
E
A
T
I
N
G
Capacity
kW
– 14.0 14.0 – – – 3.4 16.0
BTU/h
– 47800 47800 – – – 11600 54600
Current A
– 2.62 2.70 – 15.0 14.1 – –
Input power
W
– 590 640 – 3.235k 3.185k – –
TOTAL W
– – 3.825k 3.825k 1.095 5.275k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
– – – –
3.66/3.60/-
3.66 3.11 3.03
Power factor %
– – – – 94 94 – –
Noise indoor
dB-A (H/M/L)
51/49/47 – – –
Power Level dB
73/71/69 – – –
Noise outdoor
dB-A (H/L)
– 55/– – –
Power Level dB
– 71/– – –
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
– –
Max Current (A) / Max Input power (W)
– 2.9/660 3.0/710 – 30.0/6500 30.0/6800 –
Starting current (A) / Comp output (W)
– – – –
18.2/3.00k 17.2/3.00k
–
Network Impedance (ΩMAX.)
– – –
Fan motor output (Indoor/Outdoor) W
440 120 –
Moisture removal volume L/h(Pt/h)
9.0 (18.9) – –
External static pressure Pa
100 (MIN10 – MAX150) – –
Indoor
Air ow
Cooling m
3
/min (ft
3
/min)
60/50/42 (2119/1766/1483) – – –
Heating m
3
/min (ft
3
/min)
60/50/42 (2119/1766/1483) – – –
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min)
–
89.0 (3143)
– –
Heating m
3
/min (ft
3
/min)
–
83.0 (2931)
– –
Refrigerant type / amount
g
(oz)
–
R32 2.98 k (105.1)
–
Product dimension
Height mm(inch)
430 (16–15/16) 996 (39- 7/32) –
Width mm(inch)
1100(+100)
(
43–5/16(+3–15/16))
980 (38-37/64) –
Depth mm(inch)
700 (27–9/16) 370 (14- 9/16) –
Packing dimension
Height mm(inch)
515 1134 (44-41/64) –
Width mm(inch)
1315 1095 (43-7/64) –
Depth mm(inch)
812 529 (20-53/64) –
Weight
(NET) k
g
(lb)
53
94 (207)
–
(GROSS) k
g
(lb)
61
102 (224)
–
Layers limit (actually)
6(7) 2(3) –
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C
–
Heat (DBT) 16˚C – 30˚C -15˚C – 24˚C
–
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
–
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
–
Connecting method, Standard length m(ft)
ared type, 5.0(16.4) ared type, 5.0(16.4) –
Pipe length range m (ft)
5 – 50m (16.4 – 164.0) –
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4) –
Add gas amount
g
/m (oz/ft)
45
g
/m
(0.484) –
Pipe length for additional gas m (ft)
30m (98.4) –
*1 In case it is necessar
y to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 16 18/03/29 10:19:23