1-1-21
11
Single-Type
1-1. Unit Specifications
Ceiling Type S-100PT2E5B / U-100PZ2R8
INDOOR MODEL
S-100PT2E5B
PANEL MODEL
OUTDOOR MODEL
U-100PZ2R8
Branch pipe MODEL
Performance test condition
ISO5151 / AS/NZS3823.1
Power supply
ø, Hz
1ø 50 Hz 3ø 50 Hz
V
230 V 240 V 400 V 415 V Min Max
C
O
O
L
I
N
G
Capacity
kW
10.0 10.0 3.0 11.5
BTU/h
34100 34100 10200 39200
Current A
0.67 0.65 4.15 4.00
Input power
W
80 80 2.670k 2.670k
TOTAL W
2.750k 2.750k 560 4.100k
Annual consumption TOTAL kWh *
4
1375
EER/ AEER/ STAR RATING TOTAL (W/W/-)
3.64/3.55/-
3.64 5.36 2.80
Power factor %
93 93
Noise indoor
dB-A (H/M/L)
42/37/35
Power Level dB
60/55/53
Noise outdoor
dB-A (H/L)
52/–
Power Level dB
68/–
H
E
A
T
I
N
G
Capacity
kW
10.0 10.0 3.0 14.0
BTU/h
34100 34100 10200 47800
Current A
0.67 0.65 3.55 3.40
Input power
W
80 80 2.280k 2.280k
TOTAL W
2.360k 2.360k 560 4.000k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
4.24/4.13/-
4.24 5.36 3.50
Power factor %
93 93
Noise indoor
dB-A (H/M/L)
42/37/35
Power Level dB
60/55/53
Noise outdoor
dB-A (H/L)
52/–
Power Level dB
67/–
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
Max Current (A) / Max Input power (W)
0.67/80 0.65/80
9.00/5.80k
9.00/6.05k
Starting current (A) / Comp output (W)
4.15/2.50k
4.00/2.50k
Network Impedance (ΩMAX.)
Fan motor output (Indoor/Outdoor) W
111 120
Moisture removal volume L/h(Pt/h)
6.0 (12.6)
External static pressure Pa
Indoor
Air ow
Cooling m
3
/min (ft
3
/min)
30/25/23 (1059/883/812)
Heating m
3
/min (ft
3
/min)
30/25/23 (1059/883/812)
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min)
77.0 (2719)
Heating m
3
/min (ft
3
/min)
70.0 (2472)
Refrigerant type / amount
g
(oz)
R32
2.60 k
(91.7)
Product dimension
Height mm(inch)
235 (9-1/4) 996
(39- 7/32)
Width mm(inch)
1590 (62-19/32) 980
(38-37/64)
Depth mm(inch)
690 (27-5/32) 370
(14- 9/16)
Packing dimension
Height mm(inch) 360 (14-11/64)
1134
(44-41/64)
Width mm(inch) 1655 (65-5/32)
1095
(43-7/64)
Depth mm(inch) 820 (32-9/32)
529
(20-53/64)
Weight
(NET) k
g
(lb)
40 (88) 90 (199)
(GROSS) k
g
(lb)
49 (108) 98 (216)
Layers limit (actually)
9 (10) 2 (3)
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C
Heat (DBT) 16˚C – 30˚C -15˚C – 24˚C
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8) (Liquid)
ø
9.52(3/8) (Gas)
ø
15.88(5/8)
Connecting method, Standard length m(ft)
ared type, 5.0(16.4) ared type, 5.0(16.4)
Pipe length range m (ft)
5 – 50m (16.4 – 164.0)
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
Add gas amount
g
/m (oz/ft)
45
g
/m (0.484)
Pipe length for additional gas m (ft)
30m (98.4)
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.