1-1-22
11
Single-Type
1-1. Unit Specifications
Ceiling Type S-125PT2E5B / U-125PZ2R5
INDOOR MODEL
S-125PT2E5B
PANEL MODEL
OUTDOOR MODEL
U-125PZ2R5
Branch pipe MODEL
Performance test condition
ISO5151 / AS/NZS3823.1
Power supply
ø, Hz
1ø 50 Hz 1ø 50 Hz
V
230 V 240 V 230 V 240 V Min Max
C
O
O
L
I
N
G
Capacity
kW
12.5 12.5 3.2 13.5
BTU/h
42700 42700 10900 46100
Current A
0.86 0.83 16.9 16.2
Input power
W
110 110 3.650k 3.650k
TOTAL W
3.760k 3.760k 600 4.880k
Annual consumption TOTAL kWh *
4
1880 -
EER/ AEER/ STAR RATING TOTAL (W/W/-)
3.32/3.27/2.0
3.32 5.33 2.77
Power factor %
94 94
Noise indoor
dB-A (H/M/L)
46/40/36
Power Level dB
64/58/54
Noise outdoor
dB-A (H/L)
55/–
Power Level dB
70/–
H
E
A
T
I
N
G
Capacity
kW
12.5 12.5 3.3 15.0
BTU/h
42700 42700 11300 51200
Current A
0.86 0.83 14.3 13.7
Input power
W
110 110 3.100k 3.100k
TOTAL W
3.210k 3.210k 600 4.400k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
3.89/3.82/3.0
3.89 5.50 3.41
Power factor %
94 94
Noise indoor
dB-A (H/M/L)
46/40/36
Power Level dB
64/58/54
Noise outdoor
dB-A (H/L)
55/–
Power Level dB
70/–
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
Max Current (A) / Max Input power (W)
0.86/110 0.83/110
29.0/6300 29.0/6600
Starting current (A) / Comp output (W)
16.9/2.80k 16.2/2.80k
Network Impedance (ΩMAX.)
Fan motor output (Indoor/Outdoor) W
111 120
Moisture removal volume L/h(Pt/h)
7.9 (16.6)
External static pressure Pa
Indoor
Air ow
Cooling m
3
/min (ft
3
/min)
34/28/24 (1201/989/848)
Heating m
3
/min (ft
3
/min)
34/28/24 (1201/989/848)
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min)
86.0 (3037)
Heating m
3
/min (ft
3
/min)
78.0 (2754)
Refrigerant type / amount
g
(oz)
R32 2.98 k (105.1)
Product dimension
Height mm(inch) 235 (9-1/4) 996 (39- 7/32)
Width mm(inch) 1590 (62-19/32) 980 (38-37/64)
Depth mm(inch) 690 (27-5/32) 370 (14- 9/16)
Packing dimension
Height mm(inch) 360 (14-11/64) 1134 (44-41/64)
Width mm(inch) 1655 (65-5/32) 1095 (43-7/64)
Depth mm(inch) 820 (32-9/32) 529 (20-53/64)
Weight
(NET) k
g
(lb) 40 (88)
94 (207)
(GROSS) k
g
(lb) 49 (108)
102 (224)
Layers limit (actually)
9 (10) 2 (3)
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C
Heat (DBT) 16˚C – 30˚C -15˚C – 24˚C
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
Connecting method, Standard length m(ft)
ared type, 5.0(16.4) ared type, 5.0(16.4)
Pipe length range m (ft)
5 – 50m (16.4 – 164.0)
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
Add gas amount
g
/m (oz/ft)
45
g
/m
(0.484)
Pipe length for additional gas m (ft)
30m (98.4)
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 22 18/03/29 10:19:24