Loading...
1-1-27
11
Single-Type
1-1. Unit Specifications
Low Silhouette Ducted Type S-71PF1E5B / U-71PZ2R5
INDOOR MODEL S–71PF1E5B
PANEL MODEL
OUTDOOR MODEL U-71PZ2R5
Branch pipe MODEL
Performance test condition ISO13253 / AS/NZS3823.1
Power supply
ø, Hz 1ø 50 Hz 1ø 50 Hz
V 230V 240V 230V 240V Min Max
C
O
O
L
I
N
G
Capacity
kW 7.1 7.1 2.0 8.0
BTU/h 24200 24200 6800 27300
Current A 0.89 0.87 9.35 8.95
Input power
W 120 120 1.960k 1.960k
TOTAL W 2.080k 2.080k 380 2.630k
Annual consumption TOTAL kWh *
4
1040
EER/ AEER/ STAR RATING TOTAL (W/W/-)
3.41/3.32/-
3.41 5.26 3.04
Power factor % 91 91
Noise indoor
dB-A (H/M/L) 35/32/26
Power Level dB 57/54/48
Noise outdoor
dB-A (H/L) 49/–
Power Level dB 67/–
H
E
A
T
I
N
G
Capacity
kW 7.1 7.1 1.8 8.6
BTU/h 24200 24200 6100 29300
Current A 0.89 0.87 7.70 7.35
Input power
W 120 120 1.590k 1.590k
TOTAL W 1.710k 1.710k 310 2.780k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
4.15/4.02/-
4.15 5.81 3.09
Power factor % 90 90
Noise indoor
dB-A (H/M/L) 35/32/26
Power Level dB 57/54/48
Noise outdoor
dB-A (H/L) 49/–
Power Level dB 67/–
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
Max Current (A) / Max Input power (W) 1.20/160 1.15/160
16.4/3.39k 16.4/3.54k
Starting current (A) / Comp output (W) 9.35/2.0k 8.95/2.0k
Network Impedance (ΩMAX.)
Fan motor output (Indoor/Outdoor) W 124 60
Moisture removal volume L/h(Pt/h) 4.2 (8.8)
External static pressure Pa 70 (MIN10 – MAX150)
Indoor
Air ow
Cooling m
3
/min (ft
3
/min) 21/19/15
(742 / 671 / 530)
Heating m
3
/min (ft
3
/min) 21/19/15
(742 / 671 / 530)
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min) 52 (1836)
Heating m
3
/min (ft
3
/min) 45 (1589)
Refrigerant type / amount
g
(oz) R32 1.45k (51.1)
Product dimension
Height mm(inch) 290 (11–13/32) 695 (27-23/64)
Width mm(inch) 1000 (39–3/8) 875 (34-29/64)
Depth mm(inch) 700 (27–9/16) 320 (12-38/64)
Packing dimension
Height mm(inch) 355 (13-31/32) 761 (29-61/64)
Width mm(inch) 1214 (47-13/16) 1049 (41-19/64)
Depth mm(inch) 850 (33-158/32) 460 (18-7/64)
Weight
(NET) k
g
(lb) 33 (73) 44 (97)
(GROSS) k
g
(lb) 41 (91) 49 (108)
Layers limit (actually) 9 (10) 3 (4)
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C
Heat (DBT) 16˚C
– 30˚C -15
˚C – 24˚C
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
Connecting method, Standard length m(ft) ared type, 5.0(16.4) ared type, 5.0(16.4)
Pipe length range m (ft) 3 – 40m (9.8 – 131.2)
Indoor unit & Outdoor unit height difference m (ft) 15m(OD located lower)/30m(OD located higher) (49.2/98.4)
Add gas amount
g
/m (oz/ft) 35
g
/m (0.376)
Pipe length for additional gas m (ft) 30m (98.4)
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 27 18/03/29 10:19:25