1-1. Unit Specifications
Low Silhouette Ducted Type S-125PF1E5B / U-125PZ2R8
INDOOR MODEL S–125PF1E5B – –
PANEL MODEL – – –
OUTDOOR MODEL – U-125PZ2R8 –
Branch pipe MODEL –
Performance test condition ISO13253 / AS/NZS3823.1
Power supply
ø, Hz 1ø 50 Hz 3ø 50 Hz
V – 230V 240V – 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW – 12.5 12.5 – – – 3.2 13.5
BTU/h – 42700 42700 – – – 10900 46100
Current A – 1.44 1.39 – 5.10 4.95 – –
Input power
W – 215 215 – 3.335k 3.335k – –
TOTAL W – – 3.550k 3.550k 600 4.820k
Annual consumption TOTAL kWh *
4
– – 1775 – – –
EER/ AEER/ STAR RATING TOTAL (W/W/-) – – – –
3.52/3.46/-
3.52 5.33 2.80
Power factor % – – – – 94 94 – –
Noise indoor
dB-A (H/M/L) 39/35/32 – – –
Power Level dB 61/57/54 – – –
Noise outdoor
dB-A (H/L) – 55/– – –
Power Level dB – 70/– – –
H
E
A
T
I
N
G
Capacity
kW – 12.5 12.5 – – – 3.3 15.0
BTU/h – 42700 42700 – – – 11300 51200
Current A – 1.42 1.38 – 4.45 4.30 – –
Input power
W – 210 210 – 2.900k 2.900k – –
TOTAL W – – 3.110k 3.110k 600 4.350k
COP/ ACOP/ STAR RATING TOTAL (W/W/-) – – – –
4.02/3.94/-
4.02 5.50 3.45
Power factor % – – – – 94 94 – –
Noise indoor
dB-A (H/M/L) 39/35/32 – – –
Power Level dB 61/57/54 – – –
Noise outdoor
dB-A (H/L) – 55/– – –
Power Level dB – 70/– – –
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP – –
Max Current (A) / Max Input power (W) – 1.75/265 1.70/265 –
10.0/6.50k 10.0/6.75k
–
Starting current (A) / Comp output (W) – – – –
5.10/2.80k 4.95/2.80k
–
Network Impedance (ΩMAX.) – – –
Fan motor output (Indoor/Outdoor) W 235 120 –
Moisture removal volume L/h(Pt/h) 7.9 (16.6) – –
External static pressure Pa 100 (MIN10 – MAX150) – –
Indoor
Air ow
Cooling m
3
/min (ft
3
/min) 34/29/23
(1201 / 1024 / 812)
– – –
Heating m
3
/min (ft
3
/min) 34/29/23
(1201 / 1024 / 812)
– – –
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min) – 86.0 (3037) – –
Heating m
3
/min (ft
3
/min) – 78.0 (2754) – –
Refrigerant type / amount
g
(oz) – R32 2.98k (105.1) –
Product dimension
Height mm(inch) 290 (11–13/32) 996 (39- 7/32) –
Width mm(inch) 1400 (55–1/8) 980 (38-37/64) –
Depth mm(inch) 700 (27–9/16) 370 (14- 9/16) –
Packing dimension
Height mm(inch) 355 (13-31/32) 1134 (44-41/64) –
Width mm(inch) 1614 (63-9/16) 1095 (43-7/64) –
Depth mm(inch) 850 (33-15/32) 529 (20-53/64) –
Weight
(NET) k
g
(lb) 45 (99) 94 (207) –
(GROSS) k
g
(lb) 54 (119) 102 (224) –
Layers limit (actually) 9 (10) 2 (3) –
Operation condition
Cool (DBT) 18
°C
– 32
°C
-10
°
C – 43
°
C –
Heat (DBT)
16
°C
– 30
°C
-15
°
C
– 24
°
C –
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5) –
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
–
Connecting method, Standard length m(ft) ared type, 5.0(16.4) ared type, 5.0(16.4) –
Pipe length range m (ft) 5 – 50m (16.4 – 164.0) –
Indoor unit & Outdoor unit height difference m (ft) 15m(OD located lower)/30m(OD located higher) (49.2/98.4) –
Add gas amount
g
/m (oz/ft) 45
g
/m (0.484) –
Pipe length for additional gas m (ft) 30m (98.4) –
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 31 18/03/29 10:19:26