EasyManua.ls Logo

Panasonic S-100PF1E5B - Page 39

Panasonic S-100PF1E5B
259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-1-32
11
Single-Type
1-1. Unit Specifications
Low Silhouette Ducted Type S-140PF1E5B / U-140PZ2R5
INDOOR MODEL S–140PF1E5B
PANEL MODEL
OUTDOOR MODEL U-140PZ2R5
Branch pipe MODEL
Performance test condition ISO13253 / AS/NZS3823.1
Power supply
ø, Hz 1ø 50 Hz 1ø 50 Hz
V 230V 240V 230V 240V Min Max
C
O
O
L
I
N
G
Capacity
kW 14.0 14.0 3.3 15.0
BTU/h 47800 47800 11300 51200
Current A 1.50 1.47 19.3 18.6
Input power
W 225 225 4.175k 4.175k
TOTAL W 4.400k 4.400k 620 5.560k
Annual consumption TOTAL kWh *
4
2200
EER/ AEER/ STAR RATING TOTAL (W/W/-)
3.18/3.14/-
3.18 5.32 2.70
Power factor % 94 94
Noise indoor
dB-A (H/M/L) 40/36/33
Power Level dB 62/58/55
Noise outdoor
dB-A (H/L) 56/–
Power Level dB 71/–
H
E
A
T
I
N
G
Capacity
kW 14.0 14.0 3.4 16.0
BTU/h 47800 47800 11600 54600
Current A 1.50 1.46 16.00 15.30
Input power
W 225 225 3.465k 3.465k
TOTAL W 3.690k 3.690k 620 5.120k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
3.79/3.73/-
3.79 5.48 3.13
Power factor % 94 94
Noise indoor
dB-A (H/M/L) 40/36/33
Power Level dB 62/58/55
Noise outdoor
dB-A (H/L) 56/–
Power Level dB 71/–
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
Max Current (A) / Max Input power (W) 1.86/285 1.81/285
30.0/6.50k 30.0/6.80k
Starting current (A) / Comp output (W)
19.3/3.00k 18.6/3.00k
Network Impedance (ΩMAX.)
Fan motor output (Indoor/Outdoor) W 235 120
Moisture removal volume L/h(Pt/h) 9.0 (18.9)
External static pressure Pa 100 (MIN10 – MAX150)
Indoor
Air ow
Cooling m
3
/min (ft
3
/min) 36/32/25
(1271 / 1130 / 883)
Heating m
3
/min (ft
3
/min) 36/32/25
(1271 / 1130 / 883)
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min) 89.0 (3143)
Heating m
3
/min (ft
3
/min) 83.0 (2931)
Refrigerant type / amount
g
(oz) R32 2.98k (105.1)
Product dimension
Height mm(inch) 290 11–13/32 996 (39- 7/32)
Width mm(inch) 1400 55–1/8 980 (38-37/64)
Depth mm(inch) 700 27–9/16 370 (14-41/64)
Packing dimension
Height mm(inch) 355 (13-31/32) 1134 (44-41-64)
Width mm(inch) 1614 (63-9/16) 1095 (43-7/64)
Depth mm(inch) 850 (33-15/32) 529 (20-53/64)
Weight
(NET) k
g
(lb) 45 (99) 94 (207)
(GROSS) k
g
(lb) 54 (119) 102 (224)
Layers limit (actually) 9 (10) 2 (3)
Operation condition
Cool (DBT) 18
°C
– 32
°C
-10
°
C – 43
°
C
Heat (DBT) 16
°C
– 30
°C
-15
°
C
– 24
°
C
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
Connecting method, Standard length m(ft) ared type, 5.0(16.4) ared type, 5.0(16.4)
Pipe length range m (ft) 5 – 50m (16.4 – 164.0)
Indoor unit & Outdoor unit height difference m (ft) 15m(OD located lower)/30m(OD located higher) (49.2/98.4)
Add gas amount
g
/m (oz/ft) 45
g
/m
(0.484)
Pipe length for additional gas m (ft) 30m (98.4)
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 32 18/03/29 10:19:26