EasyManua.ls Logo

Panasonic S-36MK2E5A

Panasonic S-36MK2E5A
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
4-2. Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power supply
Time delay
fuse or circuit
capacity
or
(A) Power supply
Time delay
fuse or circuit
capacity
Min. wire size Max. length Min. wire size Max. length
U-8MF3R7
4 mm²
*
1
56 m
*
2
25 A
6 mm²
*
1
84 m
*
2
25 A
U-10MF3R7
6 mm²
*
1
65 m
*
2
25 A
U-12MF3R7
6 mm²
*
1
59 m
*
2
30 A
U-14MF3R7
10 mm²
*
1
65 m
*
2
40 A
U-16MF3R7
10 mm²
*
1
61 m
*
2
40 A
Indoor unit
Type (B) Power supply
Time delay fuse or
circuit capacity
D1, L1, U2, Y2, K2,
T2, F2, M1, P1, R1,
E1, E2, Z1
Refer to the Installation Instructions of the indoor unit.
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring
0.75 mm²
Use shielded wiring*
3
or
2.0 mm²
Use shielded wiring*
3
Max. 1,000 m Max. 2,000 m
(D) Remote control wiring
0.75 mm²
Max. 500 m
(E) Control wiring for group control
0.75 mm²
Max. 200 m (Total)
(F) Inter-outdoor unit control wiring
0.75 mm²
Use shielded wiring
Max. 300 m
NOTE
*1 Maximum applicable wire for terminal board of outdoor unit : 22 mm²
*2 Maximum length shows a 2% voltage drop.
*3 With ring-type wire terminal
00_341136_2WAY_Eng.indb 31 2022/9/19 9:27:26

Other manuals for Panasonic S-36MK2E5A

Related product manuals