2 - 3
2WAY SYSTEM
Control Functions - Indoor Unit
2
1. Room Temperature Control
Remote controller sensor is enabled
Set temp. in remote
controller
28℃ 28℃ 28℃
Detected temp. by
sensor
30.0℃ 27.5℃ 27.0℃
Detected temp. by
body sensor
30.0℃ 27.5℃ 27.0℃
Detected temp. by
remote controller
sensor
30.0℃ 27.5℃ 27.0℃
Room temp. = temp.
detected by remote
controller sensor
30.0℃
=30.0
27.5℃
=27.5
27.0℃
=27.0
T +2.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
Remote controller sensor is enabled
Set temp. in remote
controller
20℃ 20℃ 20℃
Detected temp. by
sensor
17.0℃ 20.5℃ 21.0℃
Detected temp. by
body sensor
21.0℃ 24.5℃ 25.0℃
Detected temp. by
remote controller
sensor
17.0℃ 20.5℃ 21.0℃
Room temp. = temp.
detected by remote
controller sensor
17.0℃
=17.0
20.5℃
=20.5
21.0℃
=21.0
T +3.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
① The thermostat does not turn OFF for 3 minutes after it turns ON.
② The thermostat does not turn ON for 1 to 3 minutes after it turns OFF.
③ The thermostat does not turn OFF for 60 minutes during the test run mode. (Forced thermostat ON)
*However, the thermostat turns OFF if an alarm occurs.
ON ONOFF
Set temp.
Set temp.
Set temp.
Set temp.
-1
+1
+2
(deg)
ON ONOFF
+1
+2
-1
(deg)
ON ONOFF
-1
+1
+2
(deg)
Heating
ON ONOFF
+1
+2
-1
(deg)
Body sensor is enabled Remote controller sensor is enabled
-0.5
-0.5
Room temp.
Cooling
Room temp.
Cooling
Heating
Room
temp.
Room
temp.
Thermostat Thermostat
ThermostatThermostat
SM830204-05_2WAY SYS.indb 3 2015/01/21 17:00:33