1-5. Capacity Correction Graph According to Temperature Condition
U-125PE1E5 (For 50 Hz) / U-125PE1E8 (For 50 Hz)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
Input coefficient (%)
Capacity coefficient (%)
Input coefficient (%) Capacity coefficient (%)
Outdoor air intake temp ( °C DB)
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
140
-15
-5 5 15253545
22°CWB
19°CWB
16°CWB
22°CWB
19°CWB
16°CWB
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
140
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Outdoor air intake temp ( °C WB)
-20 -15 -10 -5 0 5 10 15
gnitaeHgnilooC
Capacity (kW)
0 2 4 6 8 101214 16
Input coefficient (%)
0
20
40
60
80
100
120
140
160
180
200
Input coefficient (%)
0
20
40
60
80
100
120
140
160
180
200
Capacity (kW)
0 2 4 6 8 1012141618
16 °CDB
20 °CDB
24 °CDB
16 °CDB
20 °CDB
24 °CDB
Outdoor unit heating capacity correction cofficient during of frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature °C WB
-20-15-10-9-8-7-6-5-4-3-2-10123456
Correction coefficient
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.