4-9
4
4-8. Fan Control during Dry Mode
The fan control during dry mode is as follows.
AABFan mode
Set temp. in remote controller
+1
-1
T (deg)
A: Fan mode set in the remote controller
B: Fan mode is L during thermostat ON, LL during thermostat OFF
For details on T, refer to “4-1. Room Temperature Control.
4-9. Ventilation Fan Output
The output of ventilation turns ON when the indoor unit turns ON. Also, when the indoor unit turns OFF,
the output of the ventilation turns OFF.
The ventilation fan can also be turned ON and OFF using the ventilation button on the remote controller.
Refer to the operating instructions supplied with the remote controller.
To enable this function, set the indoor EEPROM DN31 to “0001” in advance.
4-10. T10 Terminal
Using the T10 terminal, each indoor unit can be operated or stopped separately. Also, operating condition can be
checked.