7-5
7
Item
code
Item
Setting data
No. Description No. Description
Type
0001
4-Way Cassette (U1)
4-Way Cassette 60x60 (Y1)
0006 High-static Pressure Ducted (E1)
0005 Low Silhouette Ducted (F1)
0007 Ceiling (T1)
0008
Wall mounted (K1) 0036 Ducted (N1)
Indoor unit
capacity
0005 36 (Type 36) 0007 45 (Type 45) 0009 56 (Type 50)
0011 71 (Type 60) 0012 80 (Type 71) 0015 112 (Type 100)
0017 140 (Type 125)
0023 280 (Type 250)
0018 160 (Type 140) 0021 224 (Type 200)
System
address
0001
0002
0003
Unit No. 1
Unit No. 2
Unit No. 3
0030
0099
Indoor unit
address
0001
0002
0003
Unit No. 30
Not set
Unit No. 1
Unit No. 2
Unit No. 3
0064
0099
Unit No. 64
Not set
Group control
address
0000
0001
0002
0099
Individual (1:1 = Indoor unit with no group wiring)
Main unit (One of the group-control indoor units)
Sub unit (All group-control indoor units except for main unit)
Not set
Cooling intake
temperature
shift
–010
Shifts intake temperature by
–
10°C.
–009
Shifts intake temperature by
–
9°C.
–001
Shifts intake temperature by
–
1°C.
0000
0001
No intake temperature shift
Shifts intake temperature by +1°C.
0009
0010
Automatic
stop time after
operation start
0000
0001
0002
Shifts intake temperature by +9°C.
Shifts intake temperature by +10°C.
Function disabled
Stops automatically 5 minutes after operation starts.
Stops automatically 10 minutes after operation starts.
Can be set
in 5-minute
units.
*
0123
0124
0125
Stops automatically 615 minutes after operation starts.
Stops automatically 620 minutes after operation starts.
Stops automatically 625 minutes after operation starts.
7-4. List of Detailed Setting Items