1-5. Capacity Correction Graph According to Temperature Condition
U-100PE1E5 (For 50 Hz) / U-100PE1E8 (For 50 Hz)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
gnitaeHgnilooC
Input coefficient (%) Capacity coefficient (%)
Input coefficient (%)
Capacity coefficient (%)
Outdoor air intake temp ( °C WB) Outdoor air intake temp ( °C DB)
)Wk( yticapaC)Wk( yticapaC
Input coefficient (%)
Input coefficient (%)
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80
100
120
140
160
180
200
0 2 4 6 8 101214 16
0 2 4 6 8 1012141618
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
140
-15
-5 5 15253545
22°CWB
19°CWB
16°CWB
22°CWB
19°CWB
16°CWB
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
140
160
-20 -15 -10 -5 0 5 10 15
16 °CDB
20 °CDB
24 °CDB
16 °CDB
20 °CDB
24 °CDB
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Outdoor unit heating capacity correction cofficient during of frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature °C WB
-20-15-10-9-8-7-6-5-4-3-2-10123456
Correction coefficient
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.