5-23
5
E16 Automatic address alarm (capacity too high)
Error Detection Method
Error Diagnosis
It is judged an error the total capacity of indoor units replied by communication is more than that of outdoor units.
(This is detected even when auto address setting is not used.)
1.
2.
1
The total capacity of indoor units is more than that of outdoor units.
Conduct checks prior to auto address setting. 1-1
Auto
Address
SM830211-02PAC-i.indb23SM830211-02PAC-i.indb23 2012/07/122:09:552012/07/122:09:55