H05 Sensor failure, Compressor discharge temperature sensor (TD) disconnected
Error Detection Method
(In case of outdoor temperature over 5°C) For 10 minutes since started, variation of discharge temperature is always
detected within 2°C comparing with the temperature just before starting.
1.
•
(In case of outdoor temperature less than 5°C) For 30 minutes since started, variation of discharge temperature is
always detected within 2°C comparing with the temperature just before starting.
•
1-1
1-2
Reinstall correctly.
Yes
No
1
Sensor
Trouble
Replace the sensor with a new one.
1-2
Is the sensor properly installed at the holder side?