Aquarea air / water heat pump – design handbook 07 / 2014
Products, functions and technical data
Bi-Bloc system
Technical data
Bi-Bloc system
Series
Aquarea LT Aquarea LT
Aquarea T-CAP Aquarea HT
Phases single phase
three phase single phase three phase single phase three phase
Hydromodule
Model
WH-SDF07C3E5
WH-SDC07C3E5
WH-SDF09C3E5
WH-SDC09C3E5
WH-SDF12C6E5
WH-SDC12C6E5
WH-SDF14C6E5
WH-SDC14C6E5
WH-SDF16C6E5
WH-SDC16C6E5
WH-SDF09C3E8
WH-SDC09C3E8
WH-SDF12C9E8
WH-SDC12C9E8
WH-SDF14C9E8
WH-SDC14C9E8
WH-SDF16C9E8
WH-SDC16C9E8
WH-SXF09D3E5
WH-SXC09D3E5
WH-SXF12D6E5
WH-SXC12D6E5
WH-SXF09D3E8*
WH-SXC09D3E8
WH-SXF12D9E8*
WH-SXC12D9E8
WH-SHF09D3E5
WH-SHF12D6E5
WH-SHF09D3E8
WH-SHF12D9E8
Output capacity
Heating capacity A-15 / W35
kW 4.29 5.9 9 9.73 10.24
8.0 8.66 9.39 9.03 12.06 8.74 12.46 9.02 11.2 9 12
Power consumption A-15 / W35
kW 1.88 2.5 3.55 3.9 4.24
3.13 3.44 3.8 3.64 4.99 3.45 5.2 3.82 5.21 3.75 5.58
Coefcient of performance A-15 / W35
2.28 2.36 2.54 2.49 2.42
2.55 2.52 2.47 2.48 2.42 2.53 2.4 2.41 2.18 2.4 2.15
Heating capacity A-7 / W35
kW 5.75 6.55 10.74 11.55 12.28
9.49 10.07 10.86 9.31 12.63 9.1 12.1 9.31 11.91 9 12
Power consumption A-7 / W35
kW 1.99 2.38 3.58 3.96 4.32
3 3.53 3.93 3.27 4.62 3.11 4.51 3.35 4.65 3.33 4.8
Coefcient of performance A-7 / W35
2.89 2.75 3 2.91 2.84
3.16 2.85 2.76 2.84 2.73 2.93 2.68 2.84 2.61 2.7 2.5
Heating capacity A2 / W35
kW 6.64 7.07 11.97 12.72 13.38
8.8 11.4 12.07 9.16 11.73 8.59 11.51 8.9 11.48 9 12
Power consumption A2 / W35
kW 1.98 2.03 3.35 3.67 3.97
2.36 3.31 3.7 2.5 3.42 2.39 3.35 2.52 3.51 2.65 3.72
Coefcient of performance A2 / W35
3.35 3.48 3.57 3.47 3.37
3.73 3.44 3.26 3.67 3.43 3.59 3.44 3.53 3.27 3.4 3.23
Heating capacity A7 / W35
kW 6.96 8.76 11.86 13.92 16.02
8.5 11.38 13 9.23 12.14 8.77 11.81 9.17 11.58 9 12
Power consumption A7 / W35
kW 1.51 2.01 2.49 3.01 3.7
1.76 2.4 2.94 1.89 2.53 1.82 2.52 1.99 2.78 1.98 2.73
Coefcient of performance A7 / W35
4.62 4.37 4.76 4.62 4.34
4.82 4.75 4.42 4.89 4.79 4.84 4.68 4.79 4.29 4.55 4.4
Heating capacity A2 / W55
kW 6 9.1 9.5 9.8 9.8
8.8 9.1 9.5 9 12 9 12 9 10.8 9 10.8
Power consumption A2 / W55
kW 3.16 4.18 4.4 4.55 4.55
3.98 4.18 4.4 4.11 5.51 4.11 5.51 3.92 4.9 3.91 4.7
Coefcient of performance A2 / W55
1.9 2.18 2.16 2.15 2.15
2.21 2.18 2.16 2.19 2.18 2.19 2.18 2.3 2.2 2.3 2.3
Cooling capacity A35 / W7
kW 6 7 10 11.5 12.2
7 10 11.5 12.2 7 10 7 10
Power consumption A35 / W7
kW 2.3 2.9 3.6 4.4 4.8
2.25 3.55 4.4 4.8 2.25 3.6 2.25 3.6
Coefcient of performance (EER) A35 / W7
2.61 2.41 2.78 2.61 2.54
3.11 2.82 2.61 2.54 3.11 2.78 3.11 2.78
Unit data
Dimensions (H × W × D)
mm 892 × 502 × 353
892 × 502 × 353
Weight
kg 43 45 43 45 49 51 49 51 49 51
50 51 51 52 51 52 51 52 47 48 49 51 50 51 51 46 50 52 50 52
Water-side connection
inch AG R 1¼
R
Pump – speed stepping
3
3 7 3 7 3
Pump – power consumption (max.)
W 100 75 100 75 190
190 190 180 190 180 190 180 190 60 180 180
Volumetric ow rate of heating circuit for
A7 / W35 / 30
l / min 20.1 25.8 34.4 40.1 45.9
25.8 34.4 40.1 45.9 25.8 34.4 25.8 34.4 25.8 34.4 25.8 34.4
Minimum circulation
l / min 10 19
10 19 10 19 10 19 13 10 19 10 19
Safety valve (open / closed)
bar 3 / 2.65
3 / 2.65 3.0 / 2.65 3.0 / 2.65
Electric
Capacity of the additional electric heater
kW 3 6
3 9 3 6 3 6 3 6 3 9
Power consumption (heating / cooling)
kW 1.59 / 2.30 2.2 / 2.9 2.57 / 3.6 3.11 / 4.4 3.78 / 4.8
1.9 / 2.25 2.57 / 3.55 3.11 / 4.4 3.78 / 4.8 1.9 2.57 1.9 2.57 1.98 2.73 1.98 2.73
Operation and starting current (heating / cooling)
A 7.30 / 10.40 10.1 / 13.1 11.7 / 16.1 14.1 / 19.7 17.1 / 21.5
2.9 / 3.4 3.9 / 5.3 4.7 / 6.6 5.7 / 7.2 8.8 10.4 11.9 16.7 2.9 3.4 3.9 5.4 9.5 13 9.5 13
Power supply 1 (current consumption) A 21 22.9 24 25 26
11.8 8.8 9.4 9.9 25 29 14.7 11.9 28.5 29 32.8 29
Power supply 1 (frequency / voltage) Hz / V 50 / 230
50 / 400 50 / 230 50 / 400 50 / 230 50 / 400
Power supply 2 (current consumption) A 26
13 13 13 13 26 26 13 13 26 26 13 13
Power supply 2 (frequency / voltage) Hz / V 50 / 230
50 / 230 50 / 230 50 / 230 50 / 230 50 / 230
Power supply 3 (current consumption) A 13
13 13 13 13 13 13 13
Power supply 3 (frequency / voltage) Hz / V 50 / 230
50 / 400 50 / 230 50 / 400 50 / 230 50 / 400
Panasonic measurement data in accordance with EN 14511-2. The data is to be considered as guidance values and not as a performance guarantee
* Devices have a high efciency pump and full the criteria of the Ecodesign Directive valid from 2015 for energy-related products (ErP)
Panasonic measurement data in accordance with EN 14511-2. The data is to be considered as guidance values and not as a performance guarantee
* Devices have a high efciency pump and full the criteria of the Ecodesign Directive valid from 2015 for energy-related products (ErP)