Aquarea air / water heat pump – design handbook 07 / 2014
Project Design
Planning heat source – air
Assembly conditions and minimum distances from monobloc unit
The heat output of the monobloc unit may not be prevented by
additional protection apparatus like sun blind or similar.
Locations at which the outside temperature decreases below -20 °C
must be avoided.
The minimum clearances (see gure) must be observed.
A drainage system using a drainage pipe leading to a gravel bed
in the frost-free subsoil is recommended for draining melt water in
de-icing mode (see installation example on page 80).
Objects that can lead to short circuit of exhaust air must not be
erected.
The operational noise emission of the monobloc unit should not lead
to irritation of the users or neighbours.
- Use additional vibration-damping rubber buffers for
If the monobloc unit is installed near the sea, in regions with a high
content of sulphur or at oily locations (e.g. machine oil, etc.), its
operational service life will be possibly shortened.
For installation locations that can be inuenced by strong winds e.g.
when a wind blows between buildings, including on building, the
Monobloc unit must be secured on the building by means of an
additional protection against toppling (e.g. cable).
The monobloc unit is only developed for outdoor installation and may
not be installed outdoors.
Condensate should be able to be drained from the unit without
difculty.
Minimum distances from the Monobloc unit to the neighbouring walls and objects with
representation of air ow direction.
Assembly conditions
and minimum distances
from monobloc unit
1
Minimum distance 100 mm
2
Minimum distance 300 mm
3
Minimum distance 1,000 mm
2
1
2
3