Aquarea air / water heat pump – design handbook 07 / 2014
Products, functions and technical data
Bi-Bloc system
Technical data
Bi-Bloc system
Series
Aquarea LT
Aquarea LT Aquarea T-CAP Aquarea HT
three phase single phase three phase single phase three phase
Outdoor unit
Model
WH-UD07CE5-A
WH-UD09CE5-A
WH-UD12CE5-A
WH-UD14CE5-A
WH-UD16CE5-A
WH-UD09CE8
WH-UD12CE8
WH-UD14CE8
WH-UD16CE8
WH-UX09DE5
WH-UX12DE5
WH-UX09DE8
WH-UX12DE8
WH-UH09DE5
WH-UH12DE5
WH-UH09DE8
WH-UH12DE8
Acoustics
Sound pressure level
1
dB(A) 48 49 50 51 53
49 50 51 53 49 50 49 50 49 50 49 50
Sound power level dB(A) 66 67 67 68 70
65 66 71 68 66 67 66 67 53 53 66 67
Fan speed, top (heating / cooling) U / min 580 / 670 640 / 700 510 / 600 540 / 630 580 / 630
490 / 550 510 / 600 540 / 630 580 / 630 490 / 550 520 / 600 490 / 550 520 / 600 490 520 490 520
Fan speed, bottom (heating / cooling) U / min – – 550 / 640 580 / 670 620 / 670
530 / 590 550 / 640 580 / 670 620 / 670 530 / 590 560 / 640 530 / 590 560 / 640 530 560 530 560
Air ow rate (heating / cooling) m³ / min 46 / 56.3 51 / 56.3 80 / 93.3 84 / 97.8 90 / 97.8
76.8 / 89.5 80 / 93.3 84 / 97.8 90 / 97.8 76.8 / 89.5 80 / 93.3 76.8 / 89.5 80 / 93.3 76.8 80 76.8 80
Unit data
Dimensions (H × W × D) mm 795 × 900 × 320 1,340 × 900 × 320
Pipe diameter (liquid) mm (inch) 9.52 (3/8")
Pipe diameter (gas) mm (inch) 15.88 (5/8")
Refrigerant kg 1.45 (R410A) 2.75 (R410A)
2.75 (R410A)
2.95
(R410A)
3.1 (R410A) 2.99 (R407C)
Pipe length m 3 to 30 3 to 40
Pre-lled pipe length m 30
Additional refrigerant lling g / m 30 50
Max. height difference IG / AG m 20 30
Temperature
ranges
Operating range (outside temperature) °C -20 to 35
Operating range
(supply water temp. (H / C)
°C 25 to 55 / 5 to 20
25 to 55 / 5 to 20 25 to 65
1
Measured value in 1 m distance and in 1.5 m height
Technical data of the bi-bloc system units
Phase-out models C,D & E series