Aquarea air / water heat pump – design handbook 07 / 2014
Project Design
Heat pump selection
Example
Example
Note In a new building, the building fabric generally dries out in the rst two
years after occupancy, whereby moisture from the construction phase
escapes from the building fabric; in this phase, the heat requirement is
higher than after the building has dryed. This increase in heat require-
ment should be offset by the additional electric heater.
For a residential house in London, UK a required heating load of
9.6 kW and an outside temperature θe = -1.5 °C
Water heating for four people with a normal comfort level
(45 litres per person and day at 45 °C tap temperature or 1.8 kWh):
4 Hence 1.8 = 7.2 kWh per day. A heat pump with a heating power
of 9.6 kW would require an operating time of 7.2 kWh / 9.6 kW = 0.75 h.
Thus, if rounded up:
Tank charging = 1 h
The pipe correction factor, owing to a pipe length of 15 m
(one-way length) with means of 1.0 and 0.83 results in
line correction factor = 0.92
Total heating capacity ≥
9.6 • 24 h
=
230.4
= 10.89 kW
(24 h – 1 h) • 0.92 21.16
Factoring in power supplier outages of 2 hours per day:
Total heating capacity ≥
9.6 • 24 h
=
230.4
= 11.93 kW
(24 h – 1 h – 2 h) • 0.92 19.32
The calculated overall heating capacity must be calculated using a
continuous water supply temperature of 35 °C for a underoor heating
system.
Heat pump capacity ≥
standard heating load
24 h
(24 h – tank charging time – power supplier outage time)
pipe correction factor
Note The illustrated calculation of the overall heating load may differ slightly
from the detailed calculation of the Aquarea Designer, but can still be
used as a rule of thumb for fast calculation without the need of a calcu-
lation program.