60 
Setting 2: When heating priority is not set by control panel: 
  When Solar Priority is set/not set by control panel: 
 
1.  3 ways valve control: 
o  3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank 
heat-up interval. Both modes will switch alternatively. Tank mode is the Initial running mode of this heat 
+ tank mode (heating no priority). 
 
2.  Heat pump operation control: 
o  During heating heat-up interval 
  Follow normal heating operation 
Under solar priority set condition:
 
  Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo 
OFF AND solar 3WV OFF AND Tank temperature < THERMO ON TEMP (End Room Interval 
Early) OR  
  Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < 
THERMO ON TEMP AND solar 3WV OFF. 
Under solar priority not set condition:
 
  Switch to tank heat interval and start counting tank heat-up timer when External Room Thermo 
OFF AND Tank < THERMO ON TEMP (End Room Interval) OR  
  Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < 
THERMO ON TEMP. 
* THERMO ON TEMP is defined Tank thermo ON/OFF condition below. 
o  During tank heat-up interval 
  Heat pump tank target temperature = Tank set temperature or [50°C] whichever lower. 
  Heat pump Water Outlet set temperature is set to [53°C] during tank interval. 
  Initial Tank THERMO ON TEMP = heat pump tank target temperature + [-2°C]. 
 
Tank thermo ON/OFF characteristic:
 
o  THERMO OFF TEMP: 
1.  THERMO OFF TEMP = Heat pump tank target temperature + [0°C]. 
2.  Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due 
to water thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count 
heating heat-up interval. 
3.  Tank temperature > Tank set temperature + [2°C] for continuous 10 seconds, switch 3 way 
valve to room side. End Tank heat up interval and start count heating up interval. 
 
o  THERMO ON TEMP: 
1.  THERMO ON TEMP = Heat pump tank target temperature + [-2°C]. 
2.  After heating heat-up interval, always detect tank temperature. Switch to next tank heat-up 
interval when tank temperature < THERMO ON TEMP.