EasyManua.ls Logo

Panasonic WH-SXC12F9E8

Panasonic WH-SXC12F9E8
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83
12.15 External Room Thermostat Control (Optional)
Purpose:
1 Better room temperature control to fulfill different temperature request by external room thermostat.
Recommended external room thermostat:
Maker Characteristic
Siemen (REV200) Touch panel
Siemen (RAA20) Analog
Connection of external room thermostat:
Wire Connection and thermo characteristic of Siemen REV200:
Setting L/L1 (H) Heat Thermo L/L2 (C) Cool Thermo
Set Temp < Actual Temp Open Circuit OFF Short Circuit ON
Set Temp > Actual Temp Short Circuit ON Open Circuit OFF
Cooling
Heating
Siemen REV200
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
Indoor Unit
9 L (label)
10
11
12
L1 (label)
L2 (label)
9 : Terminal Bord No.
Wire Connection and thermo characteristic of Siemen RAA20:
Setting L/Y1 (H) Heat Thermo L/Y2 (C) Cool Thermo
Set Temp < Actual Temp Open Circuit OFF Short Circuit ON
Set Temp > Actual Temp Short Circuit ON Open Circuit OFF
Cooling
Heating
Siemen RAA20
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
Indoor Unit
9 L (label)
10
11
12
Y1 (label)
Y2 (label)
9 : Terminal Bord No.
Control Content:
External room thermostat control activate only when remote thermostat connection select YES by Indoor control
panel.
When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running cool
mode, refer thermo On/Off from cooling line feedback.
Heat pump Off immediately when receive thermo off feedback.

Table of Contents

Other manuals for Panasonic WH-SXC12F9E8

Related product manuals