EasyManua.ls Logo

P&B MPR3E5 - Page 23

P&B MPR3E5
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14/1/98 Page 21 Issue H
Fault Inhibit
This can be set to either enable or inhibit of all fault trips. Note that Thermal overload is always
enabled irrespective of this fault inhibit setting.
- Contactor Applications
In order to avoid the possibility of a contactor attempting to break a short-circuit current in excess of
its rating when this is the duty of the short circuit protective device e.g. HRC fuses, the facility is
provided to inhibit a fault trip above a set current level. This level should normally be no greater
than the rated short-circuit breaking capacity of the contactor, with allowance for a suitable safety
margin. The inhibit level can be selected in the range 400% to 1200% of In in steps of 100% by
setting the last 4 bits in the matrix below.
Example
To configure the relay such that pick up occurs at 1.1 x FLC with a fault inhibit above 900% In, then
the value set would be: 137
Action Numerical
Value
Set
Y/N
Value
Overload Pick-up Point
= 1.1 x FLC
128 Y 128
Reserved -
Reserved -
Reserved -
Fault Inhibit Value 800% 8 8
Fault Inhibit Value 400% 4 -
Fault Inhibit Value 200% 2 -
Fault Inhibit Value 100% 1 1
137
- Circuit breaker applications
For circuit-breaker controlled motors, the fault trips should be enabled and this is done by setting the
last 4 bits to the minimum value of 3.
Example
To configure the relay such that overload pick-up occurs at 1.05 x FLC with fault trips enabled for
circuit-breaker application, then the value set would be 003.

Table of Contents