Excessive Air Loss On Regenerating Tower
  - Purge pressure set too high: check specications and adjust.
  - Repressurization solenoid leaking: repair, clean, or replace.
  - Inlet valve leaking or not functioning: See inlet valve not functioning.
  - Leaking check valve: repair, clean, or replace.
  - Leaking or inoperative control solenoid: repair or replace.
  - Defective controller: repair or replace.
Exhaust Valve On Drying or Repressurizing Tower Leaking
  - Valve dirty: clean valve.
  - Defectve diaphragms or seals: rebuild valve or replace. 
  - Leaking control solenoid: repair or replace.
Excessive Pressure Drop
  - Prelter or afterlter fully saturated or collapsed: replace element.
  - Desiccant contaminated with oil: replace desiccant.
  - Excessive ow: reduce air ow rate to within product specs.
Unit Does Not Fully Pressurize
  - Purge rate too low: Adjust purge pressure setting.
  - Exhaust valve leaking: see exhaust valve leaking.
  - Purge orice or repressurization valve plugged: clean.
Back Pressure In Regenerating Tower
  - Clogged mufers: clean, repair, or replace.
  - Check valve leaking: clean, repair, or replace.
  - Purge ow too high: adjust purge pressure.
  - Leaking inlet valve: See inlet valve not functioning.
Inlet or Exhaust Valve Not Functioning
  - Bad seals or solenoid: rebuild valves with available kits or replace.
  - No output from controller: replace fuse or controller.
  - Valve dirty: rebuild or clean.
Blower not operating (TWB dryers only)
  - Overload tripped: clogged blower inlet lter; replace.
  - Blower deadheaded: determine cause.
  - V-Belts broken: replace.
Amp draw is over nameplate rating (TWB4000-9000 onl)
  - Air ow through blower is too high: choke off blower manual control valve. 
Please note: When factory assistance is required, always provide serial number, model number, and full
description of problem.