TWP/TWB200 – TWP/TWB9000
33
Factory Settings
These settings are only available to the Dryer Manufacturer’s Factory or Service Personnel and are included here for
reference only.
These settings are only available to the Dryer Manufacturer’s Factory or Service Personnel and are included here for
reference only.
Enable Shutdown Dryer on Bad Repressurization
If this setting is enabled, the dryer will alarm and regeneration will shut down if the tower pressure is not within 10
psi of the inlet pressure at the end of the repressurization time.
If this setting is disabled, the dryer will wait indenitely for the tower pressure to rise to within 10 psi of inlet pressure
before proceeding to regeneration.
Use 2% Purge Cooling (Blower Models Only). Enable to use dry purge air during cooling on blower units, otherwise,
ambient air will be used, which will result in higher dewpoint spikes after switching.