Pilot Operated Proportional DC Valve
Series D*1FE
Operation Manual
17
Parker Hannifin Corporation
D_1FE 5715-688 UK CM 18.01.2019
Parameter Description Unit
Parameter Range
Default
Setting
Comment
from up to
J8
Min supply voltage
supervision
V
17 28
18
J9
Relay time out off range
min supply voltage
ms
0 3200
1000
J12 Errorhandling
0 = no fault acknowl-
edgment necessary;
255 = fault acknowledg-
ment necessary;
768 = no fault acknowl-
edgment + Fault
report about diag-
nosis;
1023 = fault acknowledg-
ment + Fault report
about diagnosis
768
J8
Min supply voltage
supervision
Adjustment of the minimal supply voltage:
Below this supply voltage the valve switches off with an error message.
J9
Relay time out off range
min supply voltage
Adjustment of the runtime monitoring:
The supply voltage must be at least constantly before the valve is ready
for operation.
J12
Errorhandling
Adjustment of the fault response or report:
0 = no fault acknowledgment necessary
255 = fault acknowledgment necessary
768 = no fault acknowledgment + Fault report about diagnosis
1023 = fault acknowledgment + Fault report about diagnosis
Overview for additional expert mode parameter
Individual description of additional expert parameters