5
PSE 1400-6000 60Hz
8.3 TECHNICAL DATA
Model
Weight
Refrigerant
R513A
N°
of
coolers
MIN.- MAX
Ambient Temperature
Amb
Compressed
air inlet
Tempera-
ture
In
F.L.A.[A]
460V±10%
/3Ph/60Hz
MOP MCA
Minimum
cable size
for
electrical
connection
Connections
Sound
pressure
level
Compres.
air
IN/OUT
Cooling
Water
IN/OUT
Conden.
drain
During
transport
and stockage
After
installation
Ac Wc
Kg Kg CO
2
e(t)
Kg
P.
T./S&T
CO
2
e
(t)
P.T./S&T
N° A A A Ø [mm2] - NPT-F NPT-F [dB (A)]
PSE 1400
380 2.7 1.55 3.8 2.19 1
32-122°F
(0-50°C)
41-122°F
(5-50°C)
41-149°F
(5-65°C)
14.2 30 17.5
4G10AWG
4" FLG
ANSI
150
1"
1/2"
58
PSE 1600
420 2.0 1.15 3.2 1.83 1 20.5 40 25.5
69
PSE 2000
730 7.6 4.35 7.0 4.0 2 31.6 65 39 4G8AWG
6" FLG
ANSI
150
1.1/4"
PSE 2400
770 7.0 4.01 8.5 4.87 2 37.8 80 47
4G4AWG
PSE 3000
- - - -/- -/- 2 37.8 80 47
PSE 3800
850 6.0 3.44 6.0 3.44 2 37.8 80 47
PSE 5000
1070 15 8.61 12.3 7.0 3 52.3 110 65
8" FLG
ANSI
150
PSE 6000
1210 13.0 7.45 11.0 6.3 3 59.4 125 74
Calibration values
Hot gas valve
12 - HGV
Pressure
condensation
High
pressure Switch
13-HP
Low
pressure
Switch
10-LP
Operating
Pressure
Water pressostatic
valve
3-WPV
IP
Safety
valve
Pressure Fan speed
PSE 1400-5000
35-38 psi
2.4-2.6 bar
145-188psi
10-13 bar
0 %
100 %
290psi
20 bar
14.5-29psi
1.0-2.0 bar
203psi
14 bar
232psi
16 bar
54
-
PSE 6000
320psi
22 bar