CONNECTION WIRING DIAGRAM
DANGER ELECTRICAL SHOCK
NOTES:
1 IF ANY OF THE ORIGINAL WIRES FURNISHED ARE
REPLACED, THEY MUST BE REPLACED WITH THE
SAME WIRE OR ITS EQUIVALENT
2 SEE PRICE PAGES FOR THERMOSTATS
3 USE 75 BEG COPPER CONDUCTORS FOR FIELD
INSTALLATION
4 SEE INSTALLATEON INSTRUCTIONS
FOR PROPER HEATENG AND COOLING CONNECTIONS
FOR YOUR UNET ENDOOR FAN MOTOR PLUGS
IIDO NOT DESCONNECT UNDER LOAD"
S CCH NOT USED ON ALL UNITS
6 THIS FUSE IS MANUFACTURED BY LETTELEUSE,
P/N 257003
7 UNIT FACTORY SHIPPED IN STD NODE
LEGEND
HAZARD DISCONNECT POWER BEFORE SERVICING
SCHEMATIC
IF USED_
CCH 208/230 1 60
IF tSED_
BLK DR _ OFM
L >_ BLK_BLK_BLK_ COLOR COUE
PI IF USED y_YEL_ } BLuBLK BLuEBLACK
F USED 8L GRN GREEN
-- RINK
RED RED
VIO VIOLET
COMPRESSOR PLUG-- MP WHT WHITE
COOLING FAN LOGIC
i t T_+90
ENERGIZED DE ENERGIZED
HEATING FAN LOGIC
ENERGIZED DE ENERGIZED
DIP SWITCH SETTINGS
DEFAULT
30 MINUTES 60 MINUTES 90 MIKUTES 120 _INUTES
FIELD SELECTADLE OPTIONS FOR TIME PERIOD
BETWEEN DEFROST CYCLES (MINUTES)
S_IL#D_ JUMPERED TEST PENS (USE METAL
OBJECT) FIELD SPEEb UP CYCLE
I) MOMENTARILY SHORT PINS AND RELEASE TO BYmASS
COMPRESSOR OFF DELAY
2) SHORT FOR 5+ SEC AND RELEASE FOR FORCED DEFROST
3) PERMANENT SHORT WELL BE IGNORED
DEFROST WILL TERMINATE IN 30 SEC IF DFT OPEN
DEFROST WILL TERMINATE NORMALLY IF DFT IS CLOSED
THE COMPRESSOR WILL SHUT OFF FOR 30 SEC ON DEFROST
ENITIATION AND TERMENATION IN THE "QUIET SHEFT" ON
POSITEON
Fig. 11 - Connection Wiring Schematics 208/230-1-60