MAN 06 033774 – technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 16/27
Reading of power factor phase 1 (address Hex. 330) : PF1 = 0,99 Inductive
Master request :
Slave
Function
Address
Address
Number of words
Number of
words
CRC16
High-order
Low-order
High-order
Low-order
07
03
03
30
00
02
C426
DIRIS reply::
Slave
Function
Number of
Word1
Word 2
CRC16
bytes
07
03
04
0000
03E7
DC89
999 /1000
Reading of power factor phase 1 (address Hex. 330) : PF1 = 0,94 Capacitive
Master request :
Slave
Function
Address
Address
Number of words
Number of
words
CRC16
High-order
Low-order
High-order
Low-order
07
03
03
30
00
02
C426
DIRIS reply:
Slave
Function
Number of
Word1
Word 2
CRC16
bytes
07
03
04
FFFF
FC54
DCE8
4294966356 / 1000
If the answer corresponds to a negative value, the answer, in decimal value, will be higher
than 1000.
In that case, it is necessary to convert the value in the following way:
First step: convert the value Hexadecimal into
binary
Hexadecimal :
FFFFFC54
Binary :
1111 1111 1111 1111 1111 1100 0101 0100
Second step: reverse the binary
value :
Binary :
1111 1111 1111 1111 1111 1100 0101 0100
opposite :
0000 0000 0000 0000 0000 0011 1010 1011
Third step: Add + 1
opposite :
0000 0000 0000 0000 0000 0011 1010 1011
+1

Other manuals for PeakTech 4145

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PeakTech 4145 and is the answer not in the manual?

PeakTech 4145 Specifications

General IconGeneral
BrandPeakTech
Model4145
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals