WAYNE BURNER WITH 100 PSI PUMP PRESSURE
Boiler Burner Air Cone Nozzle Start-UpSettings
ModelNo, ModelNo, I,D, Size FlameLock Off-CycleDamp, Air Shutter
EC/ECT-03-075 HS 21/2" NoHoles .7580° A DEL 1 1.0 .50
EC/ECT-03-100 HS 21/2" NoHoles 1.0080" B DEL 1 1.2 1.50
EC/ECT-03-120 HS 21/2"NoHoles 1.2080° B DEL 11/2 1.5 1.75
EC/ECT-04-125 HS 21/2" 6 Holes 1.2580° B DEL 1 2.0 2.00
EC/ECT-04-150 HS 21/2" 6 Holes 1.5080° B DEL 3 2,0 2.25
EC/ECT-04-175 HS 21/2" 6 Holes 1.7580° B DEL 5 2,0 2.50
EC/ECT-05-175 HS 21/2" 6 Holes 1.7580° B DEL 5 2.0 2.50
EC/ECT-05-200 HS 21/2" 6 Holes 2.00 80° B DEL 5 2,0 3.50
EC/ECT-05-250 HS 21/2" 6 Holes 2.50 80° S DEL 8 2.0 5.00
EC/ECT-06-275 HS 3-5/16" Str.Bore 2.75 80° B DEL 2 2,0 4.00
EC/ECT-06-300 HS 3-5/16'` Str.Bore 3.00 80° B DEL 2 2.0 4.50
CARLIN BURNER
Boiler Burner Start-UpSettings
ModelNo. ModelNo. Air Shutter NozzleSize PumpPressure HeadDim.A Air Band
EC/ECT-04-125 *99FRD Blank 1.00x 70° B DEL 150 PSI 2 40%open
EC/ECT-04-150 *99FRD Blank 1.25x 60° B DEL 150 PSI 3 60%open
EC/ECT-04-175 *99FRD Blank 1,50x 60° B DEL 150 PSI 4 100%open
EC/ECT-05-175 *99FRD Open 1,50x 60° B HAGO 150 PSI 5 10%open
EC/ECT-05-200 *99FRD Open 1,65x 60° B HAGO 150 PSI 5 45%open
EC/ECT-05-250 *99FRD Open 2,00 x 60° B HAGO 150 PSI 8 100%open
EC/ECT-06-275 102CRD Open 2,75x 60° B DEL 100 PSI 7 100%open
EC/ECT-06-300 102CRD Open 3,00x 60° B DEL 100 PSI 9 100%open
*Model99FRDBurnerEquippedwithModel98022PSCMotor
CARLIN EZ-IHP OILBURNERWITHMODEL98022PSC MOTOR
Boiler Burner Start-UpSettings
ModelNo, FiringRate ModelNo, AirShutter NozzleSize PumpPressure AirBand HeadBar
EC/ECT-03-075 .75 EZ-1HP Blank 0.60 x70° B DEL 150 PSI 0.55 0.60- 0.65
EC/ECT-03-100 1.00 EZ-1HP Blank 0.85 x70° A DEL 150 PSI 0.65 0.85- 1.00
EC/ECT-03-120 1.20 EZ-1HP Blank 1.00 x70° A DEL 150 PSI 0.80 0,85- 1.00
BECKETTBURNERWITH140 PSIPUMPPRESSURE
Boiler Burner Burner Static Nozzle Start-UpSettings Head
ModelNo. ModelNo. Head Plate Size AirShutter AirBand Setting
AFG-LI* LI* 33/8" .6560" B HAGO 9.0 2 N/A
AFG-L1 L1 33/8" .8560° B HAGO 10.0 1 N/A
AFG-L1 L1 ** 1.0060° B HAGO 9.0 2 N/A
AFG-F6 F6 23/4" 1.1080° A DEL 5.0 1 N/A
AFG-F6 F6 23/4" 1.2580° B HAGO 8.0 1 N/A
AFG-F6 F6 23/4" 1.5080° B HAGO 10,0 3 N/A
AFG-MV1 M-V1-3 -- 1.5060° B HAGO 10.0 3 3
AFG-MV1 M-V1-3 -- 1.7560° B HAGO 10,0 9 3
AFG-MV1 M-V1-5 -- 2.00 45° BHAGO I 0.0 5 5
CF-375 L1-S -- 2.25 450P HAGO 10.0 6 2
CF-375 L1-S -- 2.50 45° P HAGO 10.0 6 3
EC/ECT-03-075
EC/ECT-03-100
EC/ECT-03-120
EC/ECT-04-125
EC/ECT-04-150
EC/ECT..04-175
EC/ECT..05-175
EC/ECT,.05-200
EC/ECT..05-250
EC/ECT..06-275
EC/ECT-06-300
* RequiresLowFiringRateBaffle ** Removestaticplatefor 1.20GPHrate.
NOTE:Aboveair settingsare start-upsettingsonly-- final adjustmentsare to bemadewithcombustiontest instruments.Adjustburnerfor
highestCO2 (Maximum13%)whilemaintaininga 0 smokeand -.01to -.02ovediredraft.