EasyManua.ls Logo

PEERLESS WV-DV - Page 12

PEERLESS WV-DV
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Table 5.1
Beckett NX Burner Specifications
Boiler Model No. Burner Model Nozzle Manufacturer, Size Pump Pressure (psig) Head/Air Setting Low Fire Baffle
WV-DV-03-075 NX70LB Delavan 0.60 60° W¹ 175 2.25 Ye s
WV-DV-03-085 NX70LB Delavan 0.65 60° W 175 3.00 Ye s
WV-DV-03-110 NX70LB Hago 0.85 60° B¹ 175 3.75 No
WV-DV-04-115 NX70HB Hago 0.85 60° B 170 1.50 Ye s
WV-DV-04-130 NX70HB Hago 1.00 60° B¹ 170 1.50 No
Table 5.2
Table 5.3
Carlin EZ1-HP Burner Specifications
Boiler Model No. Delavan Nozzle Size Pump Pressure (psig) Air Boot Setting Head Bar
WV-DV-03-075 .60 70° A¹ 150 0.5 0.75
WV-DV-03-085 .65 70° A¹ 150 0.6 0.75
WV-DV-03-110 .85 70° A 150 0.85 1.10 - 1.25
WV-DV-04-115 Hago 1.00 60° B¹ 140 1.00 1.10 - 1.25
WV-DV-04-130 Hago 1.10 60° B 140 1.25 1.10 - 1.25
Riello BF5 Burner Specifications
Boiler Model No. Nozzle Size Pump Pressure (psig) Turbulator Setting Air Damper Setting
WV-DV-03-075 Delavan .60 80° B¹ 165 1 3.3
WV-DV-03-085 Delavan .65 80° B¹ 165 1 3.8
WV-DV-03-110 Delavan .90 80° B 165 2 5.0
WV-DV-04-115 Hago .85 60° B¹ 180 2 5.0
WV-DV-04-130 Hago 1.10 60° B 140 4 5.0
Start-up and adjustment recommendations: Above Turbulator, Pin, Air Damper, and Air Dial settings are start-up settings only. Adjust burner for highest
CO
²
(no more than 13%) while maintaining a 0 smoke spot. Pressure or draft over fire and in flue cannot be adjusted. However, draft and/or pressure
measurements must be taken in these two locations and recorded for reference. All adjustments and measurements must be made using suitable
instruments such as those found in a Bacharach Combustion Test Kit.
Factory Installed Nozzles are indicated in Boldface.
1. Shipped Loose
OIL BURNER

Related product manuals