Correction factor for the SET button
during night operation (energy saving)
(with In1 or In2 = 8 or -8)
During night operation the control set is:
Set Control = Set + nSC
In night mode decimal point flashes.
8 = Night mode digital input (energy saving,
N.O.)
7 = Stop defrosting remotely (N.O.) (reads
rising edge of impulse)
6 = Start defrosting remotely (N.O.) (reads
rising edge of impulse)
5 = Stand-by remotely (N.O.) (In order to
indicate Stand-By mode, the display shows
‘In5’ alternating with the current view)
4 = Pump-down pressure switch (N.O.)
3 = Man-in-room alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man-in-room alarm (N.C.)
-4 = Pump-down pressure switch (N.C.)
-5 = Stand-by remotely (N.C.) (In order to
indicate Stand-By mode, the display shows
‘In5’ alternating with the current view)
-6 = Start defrosting remotely (N.C.) (reads
falling edge of impulse)
-7 = Stop defrosting remotely (N.C.) (reads
falling edge of impulse)
-8 = Night mode digital input (energy saving,
N.C.)
0 = only display set point
1 = display set point, AUX, light access
2 = access in programming not permitted
3 = access in second level programming not
permitted