System 450™ Series Control Modules with Analog Outputs Installation Instructions
19
Figure 5 shows an example of the analog output setup values and the resulting output signal in a typical space
heating application (SP > EP and OSP < OEP).
The control action between the input signal and the output signal can be set up four ways, depending on the values
selected for the Setpoint (SP), End Point (EP), Percent Output Signal Strength at Setpoint (OSP), and Percent
Output Signal Strength at End Point (OEP). The LCD displays different Control Ramp icons for the four control
actions.
Table 9 shows the four Control Ramp icons and the associated analog output setup value relationships.
System Output
Condition Value
Less Greater
65°F
10%
70°F
SP > EP
SP = 70 ( )
EP = 65 ( )
OSP = 10 (%)
OEP = 100 (%)
OSP
SP
EP
Proportional
Band
Fig:sys450_cntrl_rmp_exmpl
Figure 5: Control Ramp Example for a Typical
Heating Application (SP > EP and OSP < OEP)