7.1.3 USER MENU 3: CALIBRATION OF THE FLOOR
TEMPERATURE (OFFSET VALUE)
To adjust the floor-sensor temperature to the real
conditions of the floor surface, you can make an
OFFSET to the temperature measured by the floor
sensor (T
floor
see User Menu 2: Service read out).
Use a separate thermometer that you position
on the surface of the floor (T
surface
). Once the floor
temperature is stable, read the temperature
on the thermometer and calculate the offset.
OFFSET = T
floor
- T
surface
. Fill in the OFFSET VALUE in
this menu by using
[ ]
R
C
EcoHome
EcoOffice
Standby
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
or
[ ]
R
C
EcoHome
EcoOffice
Standby
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
.
Possible values: 0 to 10°C
Factory set value: 4°C
T
surface
T
floor sensor
Figure 24
7.1.4 USER MENU 4: CALIBRATION OF THE ROOM
TEMPERATURE (SET VALUE)
To adjust the room-sensor temperature to the real
conditions of the room, you can use the calibration
of the temperature set value. Use a separate
thermometer that you position in the middle of
the room (away from direct sunlight). Once the
temperature is stable, read the temperature on the
thermometer and fill in this temperature in this
menu by using
[ ]
R
C
EcoHome
EcoOffice
Standby
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
or
[ ]
R
C
EcoHome
EcoOffice
Standby
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
0h
3
6
9
12
15
18
21
24
.

Other manuals for Pentair NRG-Temp

Related product manuals