4. Installation of the sensor
90°
A
B
C
D
20 mm
Location
as indicated in the system design documentation
not on valves, flanges, supports, pumps or other heat sinks
at the top of the pipe for thermally sensitive pipe contents (A)
on lower quadrant of pipe 90° for single heating cable (B)
on lower quadrant of pipe centrally between the heating cables if
they are two or more (C)
Attachment of the sensor
fix sensor firmly on surface with adequate fixing tape (same tape as
used to fix heater to the pipe) in two places (D)
fix sensor parallel to pipe (D)
route sensor cable and eventual extension cable to avoid damage in
use� Fix to pipe with adequate tape where appropriate�
Warning: Do not install sensor at ambient temperatures below –20°C� Do
not bend sensor (last 50 mm), keep it straight under all circumstances�
Min� bending radius for sensor cable: 10 mm�
Wiring sensor to RAYSTAT-CONTROL-10
Enter the sensor cable through the indicated M16 gland 5 and wire as
shown in the wiring diagram (page 37)� Please pay attention to color
coding of the wiring�

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pentair RAYCHEM RAYSTAT-CONTROL-10 and is the answer not in the manual?

Pentair RAYCHEM RAYSTAT-CONTROL-10 Specifications

General IconGeneral
BrandPentair
ModelRAYCHEM RAYSTAT-CONTROL-10
CategoryThermostat
LanguageEnglish

Related product manuals