EasyManua.ls Logo

Pentair RAYCHEM RAYSTAT-CONTROL-10 - Description & Technical Data

Pentair RAYCHEM RAYSTAT-CONTROL-10
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
DESCRIPTION
RAYSTAT-CONTROL-10 is an electronic Pt 100 control thermostat with
display, advanced alarm facilities and the capability of switching large
currents (25 A)� The RAYSTAT-CONTROL-10 is designed to control
Pentair Thermal Management heating cable systems� Heating cable
can be controlled (switched ON/OFF) either directly by the RAYSTAT-
CONTROL-10 or via a contactor
Direct switching of heating cables is possible for heating loads up to 25 A�
For heating loads greater than 25 A indirect switching via a suitably rated
contactor controlled by a RAYSTAT-CONTROL-10 is necessary� Installation
and all wiring must be in accordance with applicable regulations� The
device must be installed in non hazardous areas only� Pentair Thermal
Management offers other controls for use in hazardous areas�
Technical data
Supply voltage: 230 Vac� +10%/–10%, 50/60 Hz (6V
leakproof maintenance-free non-
rechargeable battery incl� for programming
without power supply)
Main relay: max� 25 A, 250 Vac� Resistive
Heater operation on
sensor error: programmable: ON or OFF
Hysteresis: programmable: 1K to 5K
Set point T range: 0°C to + 150°C
Accuracy: ±0,5 K at 5°C
Operating Temperature: –30°C (–20°C, VDE approved) to +40°C
ambient
User interface: 4 x 7 segment digital display
4 push buttons
alarm relay, max� 2 A, 250 Vac�
(Potential free)
Power terminals: 3 x 0,75 mm² to 4 mm²
Alarm terminals: (3 + ) x 0,75 mm² to 2,5 mm²
Sensor terminals: (3 + ) x 0,75 mm² to 2,5 mm²
Heater terminals: (2 + ) x 0,75 mm² to 4 mm²
Enclosure
Exposure Temperature: –40°C to +80°C
Ingress Protection: IP 65
Entries: 2 x M25, 1 x M20, 1 x M16
Size: 120 x 160 x 90 (mm)
Weight: approx� 800 gr
Material: polycarbonate
Lid fixing: 4 captive screws