Pentair RAYCHEM RAYSTAT-CONTROL-10 - Functional Description; Display

Pentair RAYCHEM RAYSTAT-CONTROL-10
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Mounting: on a wall or directly on the pipe using
support brackets, SB-100 / SB-101 /
SB-110
T sensor
Type: 3-wire Pt 100 according to IEC Class B
Sensor head: 50 mm x 5 mm
Cable length: 3 m*
Cable diameter: 4 mm
Cable exposure T: –40°C to +150°C
(+215°C intermittent 1000h)
* The sensor cable can be extended with a 3-core shielded cable of 20 Ω
max� per conductor (e�g� up to 150 m with a 3x1�5 mm² cable)�
The shield shall be earthed on the controller side only
FUNCTIONAL DESCRIPTION
During normal operation, the display alternates between the measured
temperature and the set point temperature�
When the measured pipe temperature exceeds the programmed setpoint
value plus hysteresis, the switching contact opens and the heating cable
is switched off
When the measured pipe temperature falls below the setpoint value
minus hysteresis, the switching contact closes� A LED in the display
indicates that the heating cable is switched on�
In the event of an error, the alarm relay switches and an error code shows
on the display� It is possible to program the status of the heating cable (on
or off) in case of a sensor error
The unit is fitted with a battery so that programming can be done on
the bench prior to mounting in the working location (see Operational
description, page 11)�
DISPLAY
RAYSTAT-CONTROL-10 has a digital display� The three left hand digits 9a
are the value display and the right hand digit 9b is the status display
There are 4 different display modes possible:
1� In the normal operation mode (no error condition), the measured
temperature or the set point temperature value are displayed in the
value display (alternating)�