EasyManua.ls Logo

Pepperl+Fuchs KCD2-UT2-1 - Assumptions

Pepperl+Fuchs KCD2-UT2-1
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2018-02
10
Functional Safety KCD2-UT2-(Ex)1, HiC2081
Planning
3.2 Assumptions
The following assumptions have been made during the FMEDA:
Failure rate based on the Siemens standard SN29500.
Failure rates are constant, wear is not considered.
Failures during configuration are not considered.
The collective error message output is not considered in the FMEDA and in the
calculations.
Propagation of failures is not relevant.
External power supply failure rates are not included.
The collective error message output is not safety relevant.
The indication of a dangerous failure (via fault bus) is detected within 1 hour by the
programmable logic controller (PLC).
The safety-related device is considered to be of type B device with a hardware fault
tolerance of 0.
The device will be used under average industrial ambient conditions comparable to the
classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar to
IEC/EN 60654-1 Class C with an average temperature over a long period of time of 40 ºC
may be assumed. For a higher average temperature of 60 ºC, the failure rates must be
multiplied by a factor of 2.5 based on experience. A similar factor must be used if frequent
temperature fluctuations are expected.
The application program in the programmable logic controller (PLC) is configured to detect
underrange and overrange failures. These failures have been classified as dangerous
detected failures.
SIL 2 Application
The device shall claim less than 10 % of the total failure budget for a SIL 2 safety loop.
For a SIL 2 application operating in low demand mode the total PFD
avg
value of the SIF
(Safety Instrumented Function) should be smaller than 10
-2
, hence the maximum
allowable PFD
avg
value would then be 10
-3
.
For a SIL 2 application operating in high demand mode the total PFH value of the SIF
should be smaller than 10
-6
per hour, hence the maximum allowable PFH value would then
be 10
-7
per hour.
The IEC/EN 61511-1 section 11.4.4 allows devices to be used in applications one SIL
higher than given by table 3 of IEC/EN 61508-2, if the device is proven-in-use. The
assessment and proven-in-use demonstration lead to the result that the device may be
used in applications up to SIL 2. However, it is the responsibility of the end-user to decide
on applying proven-in-use devices.

Related product manuals