K-System – Signal Conditioners
Mounting and Installation
Mounting in the Non-Hazardous Area
Mounting the Signal Conditioner
Snap the device onto the DIN mounting rail in a vertical downward movement.
See following figure.
Mounting in Areas that Require the Equipment Protection Level Gc
Danger!
Explosion hazard from live wiring of circuits
If you connect or disconnect energized circuits in a potentially explosive atmosphere,
sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized circuits in the absence of a potentially explosive
atmosphere.
Danger!
Explosion hazard from wrong mounting
The device safety can be impaired by external environmental influences and by mechanical
stress. That can lead to sparking that can ignite a surrounding potentially explosive
atmosphere.
Mount the device in a surrounding enclosure that complies with IEC/EN 60079–0
and that is rated with the degree of protection IP54 according to IEC/EN 60529.
Danger!
Explosion hazard from exposed conductors
Exposed conductors of inadequately attached cables can cause sparks that can ignite the
surrounding potentially explosive atmosphere.
When installing the device ensure that the cables are adequately attached.