K-System – Signal Conditioners
Technical Specifications
7 Technical Specifications
7.1 Technical Data
Electrical Data
Control Circuit Signals
0/4 mA to 20 mA signal level according to NE 43
0/2 V to 10 V signal level according to NE 43
0/1 V to 5 V signal level according to NE 43
Current output HART compatible
Current input HART compatible
Digital output: active or passive electronic output 100 mA/30 V, short-circuit protected
Relay output 2 A, minimum load 1 mA/24 V
Logic level 24 V according to IEC 60946
Functional isolation or safe isolation according to IEC 61140 and NAMUR NE 23
Field Circuit Signals
Transmitter power supply up to 17 V DC
Current output HART compatible
Pt100, 2-, 3-, (4)-wire technology
Resistor 0 to 400 with freely definable characteristic
Potentiometer
Thermocouples of all types, internal cold junction, external reference
Current output HART compatible
Digital input according to NAMUR EN 60947-5-6
Characteristic Safety Values
MTBF: Mean Time Between Failures
Conformity
General
EMV according to
EN 61326-1
EN 61326-3-2, only for devices with SIL rating, where the data sheet mentions
this standard.
If you operate the device with a DC supply voltage, you must ensure that the bridging
of the 20 ms voltage interruption is realized by the power supply.
NAMUR NE 21
If you operate the device with a DC supply voltage, you must ensure that the bridging
of the 20 ms voltage interruption is realized by the power supply.
RoHS, refer to declaration of conformity of the respective device