K-System – Signal Conditioners
Technical Specifications
2023-03
41
LEDs according to NAMUR NE 44
Software according to NAMUR NE 53
Switch-on pulse suppression
K*D0 devices:
Supply voltage 24 V DC, loop powered
K*D2 devices:
Supply voltage 20 V DC to 30 V DC via Power Rail or supply terminals
Collective error message via Power Rail
K*A devices:
Supply voltage 115 V/230 V AC, details see datasheet
K*U devices:
Supply voltage 24 V DC or 115/230 V AC, details see datasheet
Safety devices according to VDE 0660, part 209, AK according to DIN 19250
Digital Inputs and Outputs according to NAMUR
IEC/EN 60947-5-6: Low voltage switch gear and control gear part 5 and 6:
Control devices and switching elements DC interface for proximity sensors and switch
amplifiers (NAMUR), 1999
Ambient Conditions
Ambient Temperature
-20 °C to 60 °C (-4 °F to 140 °F), exceptions see data sheets
extended ambient temperature range up to 70 °C (158 °F), necessary mounting conditions
see chapter 1.1
Storage Temperature
-40 °C to 90 °C (-40 °F to 194 °F), exceptions see data sheets
Reference Conditions for Adjustment
20 °C (68 °F)
Relative Humidity
max. 95 % without moisture condensation
Corrosive gas durability
according to ISA-S71.04, group A, severity level G3 (harsh)
Altitude
max. 2000 m
Vibration Resistance
according to EN 60068-2-6, 10 Hz to 150 Hz, 1 g, high crossover frequency
Shock Resistance
according to EN 60068-2-27, 15 g, 11 ms, half-sine