SAFETY MANUAL SIL KFD2-UT2-(EX)*, HID2082
Introduction
1Introduction
1.1 General Information
This manual contains information for application of the device in functional safety
related loops.
The corresponding data sheets, the operating instructions, the system
description, the Declaration of Conformity, the EC-Type-Examination Certificate,
the Functional Safety Assessment and applicable Certificates (see data sheet)
are integral parts of this document.
The documents mentioned are available from www.pepperl-fuchs.com or by
contacting your local Pepperl+Fuchs representative.
Mounting, commissioning, operation, maintenance and dismounting of any
devices may only be carried out by trained, qualified personnel. The instruction
manual must be read and understood.
When it is not possible to correct faults, the devices must be taken out of service
and action taken to protect against accidental use. Devices should only be
repaired directly by the manufacturer. De-activating or bypassing safety functions
or failure to follow the advice given in this manual (causing disturbances or
impairment of safety functions) may cause damage to property, environment or
persons for which Pepperl+Fuchs GmbH will not be liable.
The devices are developed, manufactured and tested according to the relevant
safety standards. They must only be used for the applications described in the
instructions and with specified environmental conditions, and only in connection
with approved external devices.
1.2 Intended Use
KFD2-UT2-Ex* (Ex devices)
This isolated barrier is used for intrinsic safety applications. It is designed to
connect RTDs, thermocouples, or potentiometers in the hazardous area, and
provide a proportional 0/4 mA ... 20 mA (0/1 V ... 5 V) signal to the safe area.
The barrier offers 3-port isolation between input, output, and power supply.
A removable terminal block K-CJC-** is available for thermocouples when internal
cold junction compensation is desired.
A fault is indicated by a red flashing LED per NAMUR NE44 and user-configured
fault outputs.
The device is easily programmed with the PACTware
TM
configuration software.
A collective error messaging feature is available when used with the Power Rail
system.
For additional information, refer to the manual and www.pepperl-fuchs.com.