EasyManua.ls Logo

Pepperl+Fuchs KFD2-UT2 Series - Page 19

Pepperl+Fuchs KFD2-UT2 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functional Safety KFD2-UT2-(Ex)*(-1)
Operation
2019-10
19
5.2.2 Resistance Thermometer Input (RTD)
Figure 5.2 Proof test set-up for KFD2-UT2-(Ex)*(-1) with resistance thermometer input (RTD)
Usage in Zone 0, 1, 2/Div. 1, 2 only for KFD2-UT2-Ex1(-1) and KFD2-UT2-Ex2(-1)
1-channel versions KFD2-UT2-1(-1) and KFD2-UT2-Ex1(-1) have only one channel.
Proof Test Procedure
1. Connect a RTD simulator, depending on the application.
for 4-wire connection: terminals 1, 2, 3, 4
for 3-wire connection: terminals 1, 2, 3 (channel I) and 4, 5, 6 (channel II)
for 2-wire connection: terminals 2, 3 (channel I) and 5, 6 (channel II)
2. Connect the digital multimeter terminals 7 and 8 (channel I) and 10 and 11 (channel II).
3. Set the RTD simulator sequentially to the temperature values
representing 4 mA, 12 mA, 20 mA at the output.
4. Measure the output current.
The proof test is passed if the output values are within 2 % of the output span.
1
This means:
for the 4 mA application: 3.7 mA to 4.3 mA
for the 12 mA application: 11.7 mA to 12.3 mA
for the 20 mA application: 19.7 mA to 20.3 mA
5. Apply short circuit between terminals 2 and 3 (channel I) and between
terminals 5 and 6 (channel II). Do not remove the RTD simulator. Check if a short circuit
of the cold junction compensation is detected.
The red LED is flashing. The output behavior in the event of a fault depends
on the device configuration.
KFD2-UT2-Ex2
Zone 0, 1, 2
Div. 1, 2
Zone 2
Div. 2
T
T
T
2
3
1
5
6
4
7
9-
8+
10
12-
11+
Fault
I supply
Multimeter
(mA)
Multimeter
(mA)
I
II
Supply +
Supply -
24 V DC
Power
supply
Supply
Bus
1
Additionally the loop diagnosis shall be tested to prove that the fault signaling via the current output is working
correctly. The output current in the event of a failure depends on the device configuration. Please record
this configuration and the resulting expected fault signaling current in the test report. Example: if downscale
is configured, 2.0 mA ±1 % must be measured in the event of a failure. The red LED must be flashing.

Other manuals for Pepperl+Fuchs KFD2-UT2 Series

Related product manuals