ON-LINE 1000VA / 2000VA / 3000VA
PH 9210 - PH 9220 - PH 9230 .
5. Specifications Phasak
Yes, ECO Mode Efficiency ≧95%
80~300Vac± 5% for 1000/2000/3000VA model
120~300Vac± 5%
for 1000/2000VA model
140~300Vac± 5%
for 3000VA only
140~300Vac± 5%
for 1000/2000VA model
160~300Vac± 5%
for 3000VA only
160~300Vac± 5%
for 1000/2000VA model
190~300Vac± 5%
for 3000VA only
50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz*
Transfer Time (Typically)
THD < 3% at Linear Load, < 5% at Non-linear Load @ Nominal Input
ECO Mode Voltage
Regulation
±10%, ±15% (Configurable)
Line Mode: 105~110% Overload warning only (No shutdown)
110~120% Warning, transfer to bypass after 60s
>120%Transfer to bypass immediately
Battery Mode: 105~110% Overload warning only (No shutdown)
110~120% Warning, shutdown after 10s
>120%Shutdown immediately
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
For long-run Models, NO Battery Inside.
Recharge Time (Typically)
4 Hours (inside batteries)
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Charger Failure /Over Charged, Fan failure, EPO active
32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity
Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
(1) Serial Port (RS232), (1) USB Port,
(1) Expansion Port (With optional card)