Dynalite Hardware
.......................................
Installation Guide
.......................................
Page 22
.......................................
16
th
February 2022 www.lighting.philips.com/dynalite
Third party system integration issues
Symptom
Probable cause Solution
One or both systems no longer
operate
Bus contention
(incompatibility)
Install a suitable conversion
gateway/interface (for example, a
DTK622-232).
Dynalite controls operate
intermittently
Third party system (such as
such as AMX, DMX or
Crestron) is streaming
messages and overriding
DyNet.
Install a suitable conversion
gateway/interface (for example, a
DTK622-232).
Disable or isolate DMX.
To ensure safety and prevent damage to the system, appropriate isolation shall be provided. Only SELV/Class 2
(UL) systems shall be connected to non-isolated DyNet interfaces.