Dynalite Hardware
.......................................
Installation Guide
.......................................
Page 5
.......................................
16
th
February 2022 www.lighting.philips.com/dynalite
Standard terminations
DyNet-STP-CABLE-LSZH
Color
Signal
Shield
Earth (cover with insulated sleeve)
Green/Green-White
Paralleled for Ground
Blue
Data +
Blue-White
Data
Orange/Orange-White
Paralleled for +V 12/24 VDC
Brown/Brown-White
Spare pair can potentially be used
to replace a damaged pair.
Daisy chained
First and last device
DyNet-SFLAT6-CABLE
RJ12 Pins
Color Signal
-
1
Silver
Ground
2
White
Ground
3
Red
Data +
4
Green
Data
5 Yellow +V 12/24 VDC
6
Brown
+V 12/24 VDC
-
Cat5e Ethernet cable
RJ45 Pins
Color Signal
1
Green-White
Data +
2
Green
Data
3*
Orange-White
Not connected
4
Blue
+V 12/24 Volts
5
Blue-White
+V 12/24 Volts
6*
Orange
Not connected
7
Brown -White
Ground
8
Brown
Ground
*Pins 3 and 6 may be used for Shield connection.
1 Green-white D+
2 Green D-
3 Orange-white N/C
4 Blue + V
5 Blue-whi te + V
6 Orange N/C
7 Brown-whi te GND
8 Brown GND