SpaceWise for Industrial Applications
v. 1.6
Philips Lighting North America
9
5. Application Modes
Various industrial application modes are supported within SpaceWise Technology. The default
factory setting is set as the warehouse mode (mode# 6) and since the behavior varies for each
mode, it is recommended to select the mode that closely reflects the installed application space.
See the SpaceWise Design Guide (www.philips.com/spacewise) for details.
Application
setting
Mode 6
(default):
Warehouse
Mode 7:
Gymnasium
Mode 8:
Warehouse
comfort
Mode 9:
Manufacturing
Mode 17:
Retail
Out of the box
behavior
Behavior of the luminaires before grouping or being altered via the commissioning
remote.
Power-up state
On
On
On
On
On
Hold Time
1
15 min
15 min
15 min
15 min
15 min
Background Level
30%
30%
30%
30%
70%
Prolong Time
2
Infinite
Infinite
Infinite
Infinite
Infinite
Start-up and Dim
behavior
Behavior of the luminaires after grouping.
Switch ON Level
3
60%
60%
60%
60%
70%
Background Level
10%
20%
10%
20%
70%
Hold Time
2 min
5 min
2 min
5 min
20 min
Fading to Switch
ON Level
0s
0s
0s
0s
0s
Fading to
Background Level
10s
10s
10s
10s
10s
Prolong Time
2 min
5 min
Infinite
Infinite
Infinite
Switch OFF to 0%
Yes
Yes
No. Stays at
background level
No. Stays at
background level
No. Stays at
background level
1
Hold time is the occupancy time out after which the luminaire dims from the task level to the
background level.
2
Prolong time is the time for which the luminaire stays at the background level before switching off.
3
Level at which lights turn ON before ramping up to full output or the level determined by the
daylight sensor.
Application
ON/OFF behavior
Mode
Warehouse (Default)
Auto ON/Auto OFF
6
Sporting Area
Auto ON/Auto OFF
7
Warehouse Comfort
Auto ON/Auto DIM to Background Level
8
Manufacturing
Auto ON/Auto DIM to Background Level
9