DH+/RIO OPTICAL COMMUNICATION MODULES USERS MANUAL
Copyright © 2003 by Phoenix Digital Corporation, All Rights Reserved.
CHAPTER 2
CONFIGURATION AND INSTALLATION INSTRUCTIONS
This chapter provides preparation for use and installation instructions (including unpacking and
inspection instructions), and a functional description of indicators, diagnostics and configuration
instructions.
2.1 UNPACKING INSTRUCTIONS
All Phoenix Digital fiber optic modules are shipped from the factory in shock absorbing materials.
Remove the fiber modules from the packing material and refer to the packing list to verify that all
items are present. Save the packing materials for future storage or reshipment.
NOTE: If the shipping carton is damaged upon receipt, request that the carrier’s agent
be present while the unit is being unpacked and inspected.
2.2 INSPECTION PROCEDURE
Fiber optic modules should be inspected visually for damage upon removal from the shipping
container.
2.3 INSTALLATION MOUNTING PROCEDURE
Standalone, Panelmount OCMs should be panelmounted per the mounting specifications provided
in Figure 3. All Phoenix Digital fiber optic modules are convection cooled, requiring no fan or
forced air cooling. An unobstructed air space must be maintained above and below the fiber
modules (6 inches minimum) to insure adequate convection airflow. The air at the bottom of the
fiber optic module may not exceed 60 degrees celsius (140 degrees F).
The user should follow Rockwell Allen-Bradley Installation and Mounting Procedures for
1771, 1746, and 1756 Chassis Installation... for 1771 Plug-In OCM, 1746 Plug-In OLC, and
1756 Plug-In OCX modules.
2-1